EasyManuals Logo
Home>Notifier>Control Panel>AFP-2800

Notifier AFP-2800 User Manual

Notifier AFP-2800
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
Emergency Operation
AFP-2800/2802 Manual P/N 11249 11-Mar-08 5
1 EMERGENCY OPERATION
Isolate Bells
Press: EXT BELL ISOLATE
EXT BELL ISOLATE LED will light
The Bells & Buzzer will stop
A subsequent alarm will restart the Buzzer but not the bells
The bell isolate can be toggled by pressing the button a second time
Isolate Warning System
Press: WARN SYS ISOLATE
WARN SYS ISOLATE LED will light
The warning system will stop
A subsequent alarm will restart the Buzzer but not the warning
system
The warning system isolate can by toggled by pressing the button a
second time
Acknowledging an Alarm
Select the Alarm using the PREV , NEXT buttons
Press: ACK to acknowledge
This will individually acknowledge alarms
Once all alarms are acknowledged the alarm LED will go steady
Resetting an Alarm
Select the Alarm using the PREV , NEXT buttons
Press: RESET then press ACK to confirm the resetting
This will individually acknowledge and reset alarms
Resets zone in alarm and clears all alarm inputs in the zone
If alarm is still present, the zone(s) will either stay in alarm or re-
alarm again after about 15 seconds
Isolate an Alarm
Select the Alarm using the PREV , NEXT buttons
Press: ISOL then press ACK to confirm the isolation
Isolates the point or zone in alarm and clears it’s alarm outputs
Isolating a zone automatically acknowledges and isolates all points
in the zone

Table of Contents

Other manuals for Notifier AFP-2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-2800 and is the answer not in the manual?

Notifier AFP-2800 Specifications

General IconGeneral
BrandNotifier
ModelAFP-2800
CategoryControl Panel
LanguageEnglish

Related product manuals