I/O Memory Allocation Section 9-3
199
CS/CJ-series PLC CX-SimulatorItem
Settings Function Settings Function
Baud rate
(bps)
00: 9,600
01: 300
02: 600
03: 1,200
04: 2,400
05: 4,800
06: 9,600
07: 19,200
08: 38,400
09: 57,600
0A: 115,200
Default: 00
Settings 00 and 06 through 0A
are valid when the communica-
tions mode is set to peripheral
bus.
This setting is not valid when the
communications mode is set to
NT Link.
Same as
CS/CJ-
series PLC.
No-protocol
mode delay
0000 to 270F:
0 to 99990 ms
(10-ms units)
Default: 0
This setting determines the delay
from execution of TXD(236) until
the data is actually transmitted
from the specified port.
Same as
CS/CJ-
series PLC.
CPU Unit’s
Unit Num-
ber in Host
Link Mode
00 to 1F: (0 to
31)
Default: 00
This setting determines the CPU
Unit’s unit number when it is
connected in a 1-to-N (N=2 to 32)
host link.
Same as
CS/CJ-
series PLC.
00 to FF
Default: 00
Start code: Set this start code
only when the start code is en-
abled (1) in bits 12 to 15 of 165.
Same as
CS/CJ-
series PLC.
00 to FF
Default: 00
End code: Set this end code only
when the end code is enabled (1)
in bits 8 to 11 of 165.
Same as
CS/CJ-
series PLC.
0: None
1: Code in 164
Default: 0
Start code setting:
A setting of 1 enables the start
code in 164 bits 8 to 15.
Same as
CS/CJ-
series PLC.
0: None
1: Code in 164
2: CR+LF
Default: 0
End code setting Same as
CS/CJ-
series PLC.
No-protocol
Mode
00: 256 bytes
01 to FF:
1 to 255 bytes
Default: 00
Set this value only when the end
code setting in bits 8 to 11 of 165
is “0: None.”
This setting can be used to
change the amount of data that
can be transferred at one time by
TXD(236) or RXD(235). The
default setting is the maximum
value of 256 bytes.
Same as
CS/CJ-
series PLC.
RS-232C
Port Set-
tings
Max. Unit
Number in
NT Link
Mode
0 to 7
Default: 0
This setting determines the high-
est unit number of PT that can be
connected to the PLC in NT Link
mode.
Not used.
Scheduled Interrupt
Time Units
0: 10 ms
1: 1.0 ms
Default: 0
This setting determines the time
units used in scheduled interrupt
interval settings.
Same as
CS/CJ-
series PLC.