EasyManuals Logo
Home>Omron>Touch terminals>NS7 Series

Omron NS7 Series User Manual

Omron NS7 Series
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
2-1 Connecting the Host
2-6
Supported communications
methods
PT
commu-
nications
type
Host
com-
munica-
tions
type
Supported connection methods
1:1 NT
Link
1:N NT
Links
FINS
Data
Links
Refer-
ence
page
RS-232C,
Controller
Link
RS-
232C,
Control-
ler Link
Host
PT
Serial port A
RS-232C cable
Host
Controller Link
Controller Link
Interface Unit
Specified shielded twisted-pair cable
Yes Yes Yes Yes
P.4-2
P.4-10
P.5-15
Ethernet,
Controller
Link
Ethernet,
Control-
ler Link
Host
PT
Ethernet
Host
Specified shielded twisted-pair cable
10BASE-T twisted-pair cross cable
Controller Link
Interface Unit
Controller Link
No No Yes Yes P.5-2
P.5-15
Yes: Connection is possible. No: Connection is not possible.
Note: Only when a Controller Link Interface Unit (NS-CLK21) is mounted.
The NS-AL002 is connected directly to the serial port of the PT and power is supplied
from pin 6 of the port.
When there are multiple serial ports and Ethernet Units for a single host, each port can
be used to communicate with separate PTs. This type of communications method,
however, will reduce the communications performance at the host.