EasyManuals Logo
Home>Omron>Controller>SYSMAC CV1000

Omron SYSMAC CV1000 User Manual

Omron SYSMAC CV1000
147 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #124 background imageLoading...
Page #124 background image
Appendix CHost Link Unit Memory Area Allocations
122
Number of Errors at Port 2
15 14 13 12 11 10 9 8 76543210
00
1: FCS error
1: Invalid data
1: Overrun error
1: Framing error
1: Parity error
1: Break
Word: 1500 + (25 x unit number) + 14
Bit
+14
Number of errors at port 2
Wrap Communications Test Port
15 14 13 12 11 10 9 8 76543210
00000000000000
RS-232C/RS-422 status (0: RS-232C; 1: RS-422)
Test port (0: Port 1; 1: Port 2)
Word: 1500 + (25 x unit number) + 15
Bit
+15
Results of Wrap Communications Test
The results of the tests at 1,200 to 19,200 bps are recorded in words 16 to 20. The contents is the same as that
shown below for word 16.
15 14 13 12 11 10 9 8 76543210
00000000
1: Comparison error
1: FCS error
1: Framing error
1: Overrun error
1: Parity error
1: Timeout error
1: CD check error
Word: 1500 + (25 x unit number) + 16
Bit
+16
0: Normal response 1: Error
The results for other baud rates are given in the following words.
+17: The result at 2,400 bps
+18: The result at 4,800 bps
+19: The result at 9,600 bps
+20: The result at 19,200 bps

Table of Contents

Other manuals for Omron SYSMAC CV1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CV1000 and is the answer not in the manual?

Omron SYSMAC CV1000 Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CV1000
CategoryController
LanguageEnglish

Related product manuals