83
5-18 SV READ 3
Finds the specified timer or counter instruction in the program (main program
area) starting from the specified address and reads the constant SV in 4-digit
BCD or reads the address of the word containing the SV. This command can be
used to start reading past 10K words of program memory, i.e., 6-digit addresses.
Note 1. Only the first instruction in the program after the specified address that
meets the specifications will be found.
2. Only the main program will be searched for CVM1 PCs.
3. If the PC is programmed using SFC, only action 0 will be searched. The en-
tire main program will be searched if SFC programming is not used.
Command Format
@ R%
x 10
0
x 10
1
x 102x 10
3
x 10
0
x 10
1
x 10
2
x 10
3
x 10
0
x 10
1
OP2OP1 OP4OP3x 16
0
x 10
5
FCS
Unit no.
Terminator
Header code Address Timer/Counter instruction Timer/Counter number
*s
In this case, this must be “0.”
Response Format
@ R%
x 10
0
x 10
1
OP2 OP4OP3 x 10
2
x 10
3
x 10
0
x 10
1
x 16
0
x 16
1
OP1
Unit no. FCS TerminatorHeader
code
Response
code
Operand SV
*s
Parameters Address (command): Specify the address from which to start searching for the
timer/counter instruction in six digits of BCD.
Timer/Counter instruction (command): Specify in four letters the instruction
used to create the timer/counter (see below).
Timer/Counter number (command): Specify the timer/counter number used
to define the timer/counter.
Timer/Counter instruction
Instruction Timer/Counter
b
OP1 OP2 OP3 OP4
number
T M H W HIGH-SPEED TIMER
WAIT (TMHW<015>)
000 to 0511
(CVM1-CPU01-EV2
C)
T I M W TIMER WAIT
(TIMW<013>)
(C C U0
and CV500)
0000 to 1023 (other
C N T W COUNTER WAIT
(CNTW<014>)
0000
to
1023
(other
CPUs)
T I M H HIGH-SPEED TIMER
(TIMH(015))
T T I M ACCUMULATIVE
TIMER (TTIM(120))
C N T R REVERSIBLE
COUNTER (CNTR(012))
T I M space TIMER (TIM)
C N T space COUNTER (CNT)
Note A total of four letters are required to specify the instruction. Be sure to include a
space where necessary.
SV READ 3 Section 5-18

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CV1000 and is the answer not in the manual?

Omron SYSMAC CV1000 Specifications

General IconGeneral
ManufacturerOmron
TypePLC
Memory CapacityNot specified in detail
Communication PortsRS-232C
Power Supply24 VDC or 100-240 VAC (depending on model)
Operating Temperature0°C to 55°C
Humidity10% to 90% (non-condensing)
Vibration Resistance10 to 57 Hz, 0.075 mm amplitude
Shock Resistance10 G
ModelSYSMAC CV1000

Summary

SECTION 1 Introduction

SECTION 2 Switch Settings and Communications Parameters

2-2 Host Link Unit Settings and Parameters

Details on Host Link Unit components, switches, and setting procedures.

SECTION 3 Installation

3-4 RS-232C Connections

Specifications and connection methods for RS-232C connections.

3-5 RS-422 Connections

Specifications and connection methods for RS-422 connections.

SECTION 4 Communications

4-1 Initial Communications Test

Steps for performing an initial test to verify system operability.

4-3 C-mode Commands

Details C-mode commands, protocol, blocks, and checksum calculation.

4-5 Communications Timing

Explains transmission timing in full-duplex and half-duplex communications.

SECTION 5 C-mode Commands

5-24 ERROR READ

Reads and clears PC errors.

SECTION 6 Maintenance and Troubleshooting

6-1 Maintenance

Explains maintenance methods and procedures for the Host Link System.

Appendix D Sample Programs Including Commands for Host Computer