Note: In a bridged library, the host will not be able to see the library
if the bridged drive ports are not enabled. Perform troubleshooting
procedures in the user’s guide to resolve a bridged drive problem.
Power System Behavior
3-36 StorageTek SL150 Modular Tape Library Customer Replaceable Unit Guide
Startup duration varies based upon the number of library modules. After
completion, the Home screen appears on the touch screen.
Figure 3–34 Home Screen
Illustration Legend:
1 - Library Health
4. Check the OK indicators on all CRUs.
5. Verify that the library health state is operational from the touch screen (see
Figure 3–34) or the SL150 remote interface.
If the health state is degraded or failed, consult the troubleshooting section of the
user’s guide to assist with resolving the problem.
To Validate Library Operation
1. Perform an operational check of replaced CRUs, as applicable:
Test the panel for general operation (locate light, touch screen, open the mailslot,
and so forth).
Confirm that the library recognizes the module controller (Modules area of the
touch screen or Library area of the SL150 remote interface).
2. Run the offline self tests from the SL150 remote interface (refer to the StorageTek
SL150 Modular Tape Library User’s Guide or the Help system for instructions).
3. Set the SL150 library to the online state and log out of the SL150 remote interface.