GENERAL REMARKS
7
1.7 Technical data
DESCRIPTION UM
CONDEXA HPR
35 45 55 70
G20 G31 G20 G31 G20 G31 G20 G31
Heating
Rated heat input
kW
34,90 45,00 55,00 70,00
kcal/h
30.014 38.700 47.300 60.200
Nominal heat output (80°/60°)
kW
33,99 43,88 53,60 68,24
kcal/h
29.234 37.733 46.099 58.683
Nominal heat output (50°/30°)
kW
37,31 47,30 58,25 74,19
kcal/h
32.085 40.674 50.095 63.806
Reduced heat input
kW
5,20 - 5,20 - 8,20 - 8,20 -
kcal/h
4.472 - 4.472 - 7.052 - 7.052 -
Reduced heat output (80°/60°)
kW
4,98 - 4,98 - 7,87 - 7,87 -
kcal/h
4.284 - 4.284 - 6.767 - 6.767 -
Reduced heat output (50°/30°)
kW
5,57 - 5,57 - 8,78 - 8,78 -
kcal/h
4.794 - 4.794 - 7.547 - 7.547 -
DHW
Rated heat input
kW
34,90
45,00 55,00 70,00
kcal/h
30.014
38.700 47.300 60.200
Nominal heat output (*)
kW
34,90
45,00 55,00 70,00
kcal/h
30.014
38.700 47.300 60.200
Reduced heat input
kW
5,20
-
5,20
- 8,20 - 8,20 -
kcal/h
4.472 - 4.472 - 7.052 - 7.052 -
Reduced heat output (*)
kW
5,20 - 5,20 - 8,20 - 8,20 -
kcal/h
4.472 - 4.472 - 7.052 - 7.052 -
Useful efciency Pn max - Pn min (80°/60°)
%
97,4- 95,8 97,5 - 95,8 97,5-96,0 97,5-96,0
Combustion efciency %
97,6 97,7 97,6 97,6
Useful efciency Pn max - Pn min (50°/30°) %
106,9- 107,2 105,1-107,2 105,9-107,0 106,0-107,0
Useful efciency 30% Pn max (30° return) %
108,2 107,9 107,6 107,5
Overall electric power (maximum heating output)
W
158 175 201 284
Circulator electric power (1,000 l/h) W
98 98 88 88
Category
● Country of destination
II2H3P ● (+) II2H3P ● (+) II2H3P ● (+) II2H3P ● (+)
II2H3P GB II2H3P GB II2H3P GB II2H3P GB
Voltage supply V-Hz
230-50 230-50 230-50 230-50
Protection level IP
X5D X5D X5D X5D
Stop loss W
37,0 35,0 35,0 35,0
Losses at the ue with burner off - burner on %
0,06 - 2,38 0,05 - 2,35 0,04 - 2,41 0,03-2,44
Heating operation
Maximum pressure bar
5 5 5 5
Minimum pressure for standard operation bar
0,8 ÷ 1,0 0,8 ÷ 1,0 0,8 ÷ 1,0 0,8 ÷ 1,0
Safety thermostat intervention °C
102 (±3) 102 (±3) 102 (±3) 102 (±3)
Maximum temperature °C
90 90 90 90
Selection eld of heating water temperature °C
20 ÷ 90/ 20 ÷ 45 20 ÷ 90/ 20 ÷ 45 20 ÷ 90/ 20 ÷ 45 20 ÷ 90/ 20 ÷ 45
Pump: maximum head available for the system mbar
820 820 430 430
at a ow rate of l/h
1.000 1.000 2.500 2.500
Heating circuit water content l
4,75 4,75 9,00 9,00
(+) The installation of this product is allowed only in the destination Countries contained in the data plate, regardless of
the present translation language.
9
In case of connection to a domestic hot water exchanger kit (accessory available on request) consider an additional 6.5 liters of water
with respect to the heating circuit water content.