CHAPTER 3 | FCM2041-U3 OPERATOR INTERFACE MANUAL
MAINTENANCE MODE
3-21
When No Bells is selected, there is no audible notification of Walktest events.
There is no event-type coding during the Walktest. Audible notification is the same
for Alarm, Supervisory, or any other event.
If the system has a report printer, Walktest events will be printed with the Walktest
designation “WT” and the event type. The Walktest event types are as follows:
SEPYTTNEVETSETKLAW
epyTtnevE
retnirP
noitangiseD
1SNM1SNMTW
mralAMLATW
2SNM2SNMTW
ytefaSgnidliuBGDLBTW
ycnegremEGR
METW
saGSAGTW
yrosivrepuSVPUSTW
ytiruceSCESTW
elbuorTLBRTTW
elbuorTSNMTSNMTW
sutatSTATSTW
rehtORHTOTW
Trouble conditions will continue to be reported for devices in Walktest.
Walktest Ending Sequence Five minutes before the end of the Walktest, a 15-second audible activation occurs.
When the Walktest is set for Group Bells, only audibles located in the group being
tested will sound; when set for All Bells, all of the audibles will sound. When the
Walktest is set for No Bells, only the strobes will activate. The audibles will sound in
a two seconds on - one second off pattern. The strobes will be on steady and will be
either synchronized or unsynchronized, depending on the system setting.
Do not perform any further Walktest activations after the 5-minute warning or 5
minutes prior to the expiration of the Walktest or the planned cancellation time.
Forty-five seconds before the end of the Walktest, a 45-second audible activation
occurs. When the Walktest is set for Group Bells, only audibles located in the group
being tested will sound; when set for All Bells, all of the audibles will sound. When
the Walktest is set for No Bells, only the strobes will activate. The audibles will sound
in a two seconds on - one second off pattern. The strobes will be on steady and will
be either synchronized or unsynchronized, depending on the system setting.
Zone coding will not be performed during a Walktest.

Other manuals for Siemens FCM2041-U3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FCM2041-U3 and is the answer not in the manual?

Siemens FCM2041-U3 Specifications

General IconGeneral
BrandSiemens
ModelFCM2041-U3
CategoryFire Alarms
LanguageEnglish

Related product manuals