Siemens RDF800KN.., RDF800KN/VB, RDD810KN/NF Basic documentation CE1P3174en
Smart Infrastructure 2020-02-21
5.2.3 Operation and monitoring with OZW772 web server
OZW772..
KNX TP1
Ethernet
USB Router
Internet /
Intranet
5701Z01a
Ethernet
Web browser
The OZW772 web server enables you to operate a Synco HVAC system from a
remote location (computer or smartphone) – using the HomeControl app.
The start page shows the most important data points. Navigating through menus
and paths enables you to access all data points quickly and correctly. The entire
installation can be visualized in the form of plant diagrams. Alarm and state
messages can be forwarded to different message receivers, such as e-mail, or
SMS, etc.
For details, see Commissioning Instructions CE1C5701.
5.2.4 Operation and monitoring with RMZ792-B bus
operator unit
The RMZ792-B is a communicating bus
operator unit designed for operating Synco
700 and RDF KNX devices in a KNX network.
It is suited for both fixed installation and mobile
use (e.g. for use by the service engineer).
It does not operate with third-party devices.
For details, see Basic Documentation CE1P3113.
The application cannot be displayed in the form of text, instead a number is used:
(Parameter Plant type on Basic setting menu):
0 = no application
1 = 2-pipe
2 = 2-pipe and electric heater
4 = 4-pipe
HomeControl app
for plant control
Note
:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RDF800KN Series and is the answer not in the manual?

Siemens RDF800KN Series Specifications

General IconGeneral
BrandSiemens
ModelRDF800KN Series
CategoryThermostat
LanguageEnglish

Related product manuals