Commissioning and Diagnostics
4-7
ET 200S Interface Module IM 151/CPU
A5E00058783-01
4.3 Commissioning and Startup of the ET 200S
Commissioning the ET 200S
Commission the ET 200S distributed I/O system as follows:
1. Install the ET 200S distributed I/O system
(see the
ET 200S Distributed I/O System
manual).
2. Set the PROFIBUS address on the IM 151/CPU if you don’t require stand-alone
operation
(see the
ET 200S Distributed I/O System
manual).
3. Wire the ET 200S distributed I/O system
(see the
ET 200S Distributed I/O System
manual).
4. During configuration as a DP slave, specify in the configuration software the
address areas in the IM 151/CPU via which data exchange with the DP master
is to take place (or use the ET 200S default setting; see Section 2.4).
5. Switch on the sensor supply voltage for the ET 200S.
6. If necessary, switch on the load voltage and the supply voltage for the motor
starters.
7. If necessary, switch the CPU component of the IM 151/CPU to STOP mode.
8. Download the configuration for the IM 151/CPU to the ET 200S.
9. Switch the IM 151/CPU to RUN mode.