Installing and connecting the device
3.6 Removing the device
IFP V2, IFP V2 PRO, IFP V2 ETH
Operating Instructions, 03/2023, A5E46641410-AE
73
5. Loosen the mounting clips screws and remove all mounting clips.
6. Remove the built-in device from the mounting cutout.
See also
Installing the built-in device (Page 42)
Connecting the device (Page 56)
3.6.2 Removing a PRO device
The PRO device is generally removed in the reverse order for mounting and connecting.
Procedure
Proceed as follows:
1. Switch off the power supply of the PRO device.
2. When you use the PRO device in a hazardous area, make sure that one of the two following
requirements is met: The area is no longer hazardous or the PRO device and its plug-in
connections are de-energized.
3. Depending on your device version, open the PRO device as follows:
– PRO device for support arm (not extendable, flange top) and for pedestal (extendable,
flange bottom): Loosen the 8 screws of the backplane cover and remove the backplane
cover.
– PRO device for support arm (extendable, round tube): Loosen the 2 screws of the
terminal compartment cover and remove the terminal compartment cover.
4. Remove all cable ties used for strain relief on the strain relief plate of the PRO device.
5. Remove all plug-in connectors and the equipotential-bonding cable from the PRO device.
6. Remove the PRO device from the support arm or pedestal. Make sure that the connection
cables are not damaged.
7. Depending on your device version, close the PRO device as follows:
– PRO device for support arm (not extendable, flange top) and for pedestal (extendable,
flange bottom): Fasten the backplane cover to the PRO device with the 8 screws,
torque 1.5 Nm.
– PRO device for support arm (extendable, round tube): Fasten the terminal
compartment cover to the PRO device with the 2 screws, torque 1.5 Nm.
See also
Mounting the PRO device (Page 47)
Connecting the device (Page 56)