Technical information
7.2 Electromagnetic compatibility
IFP V2, IFP V2 PRO, IFP V2 ETH
Operating Instructions, 03/2023, A5E46641410-AE
91
DNV (Det Norske Veritas)
LR (Lloyds Register)
CCS (China Classification Society)
NK (Nippon Kaiji Kyokai)
KR (Korean Register of Shipping)
After acceptance has been granted, you can find the corresponding certificates on the
Internet at the following addresses:
IFP certificates (https://support.industry.siemens.com/cs/ww/en/ps/16788/cert)
IFP PRO certificates (https://support.industry.siemens.com/cs/ww/en/ps/21662/cert)
7.2 Electromagnetic compatibility
The device fulfills, among other things, the requirements of the EMC directive applicable to
the European domestic market.
Installing the device according to EMC directive
EMC-compliant mounting of the device and the use of interference-proof cables provide the
basis for interference-free operation.
Observed the following manuals in addition to these operating instructions:
Designing interference-free controllers
(https://support.industry.siemens.com/cs/ww/en/view/59193566)
Industrial Ethernet / PROFINET - Passive network components
(https://support.industry.siemens.com/cs/ww/en/view/84922825)
Pulse-shaped disturbance
The following table shows the electromagnetic compatibility of modules with regard to pulse-
shaped interference. The precondition for electromagnetic compatibility is that the device
meets the specifications and guidelines for electrical installation.
Pulse-shaped interference Tested with Performance
level equiva-
lence
Electrostatic discharge
in accordance with
IEC 61000-4-2
Air discharge: 8 KV
3
Contact discharge: 6 kV (built-in device on the front,
PRO devices and Transceiver Unit all-round)
Contact discharge: 4 kV (built-in devices, at rear)
2
Bursts
(high-speed transient inter-
ference)
in accordance with
IEC 61000-4-4
2 kV power supply line
1 kV signal line, < 30 m
3
2 kV signal line, > 30 m
4