Commissioning, service, troubleshooting
13.4 Troubleshooting
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
295
Acknowledgment /
fault rectification
Initialization
module write-
protected,
parameter
changes not
allowed
The initialization module is
completely or partially write-
protected.
Reparameterization of
SIMOCODE pro is denied
because the initialization module
Deactivate write protection
of the initialization module
Initialization
module -
identification
data write-
protected
Reparameterization has been
rejected because the initialization
module is write-protected.
• Select a
parameterization with
identical addressing
and I&M data
• Deactivate the partial
write protection of the
initialization module
Initialization
module read
The parameters of the
initialization module were read
Initialization
module
The reparameterization was
accepted in the initialization
Initialization
module
The initialization module has
been cleared and is now back in
the as-delivered condition.
Internal
ground fault
Internal ground-fault monitoring
has responded. An impermissibly
high residual current is flowing.
Please check the motor
connection cable for
Reset Tripped 28
No start
permitted
The permissible number of starts
in the monitoring timeframe has
been attained. The next start
should not be carried out until the
interlocking time has expired.
Reset Tripped
Module fault At least 1 SIMOCODE pro
module is not ready for use.
• Connecting cable
defective or incorrectly
connected
• Module defective.
Replace the module.
See Chapter
Replacing
SIMOCODE pro
components
(Page 279).
Clear the fault;
reset
Tripped 1