Parameters
4.3 Monitoring functions
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
133
Active status of trip and warning levels
Unless deactivated, this function is always active, independent of whether the motor is
running or not (operating state "ON").
Here you can specify in which motor operating states the trip level / warning level will be
active:
Always (on)
/ warning level is always acti
ve, regardless
of whether the motor is running or at a standstill
If motor runs, except TPF (run)
/ warning level is only active when the
when the motor is on, except TPF,
with startup override (run+)
/ warning level is only active when the
motor is running and starting has been completed
Here you can set how SIMOCODE pro should respond if the trip level is overshot.
See also "Tables of responses of SIMOCODE pro" in chapter Important information
(Page 7).
Table 4- 32 Response to "trip level" in ground-fault monitoring
0 to 25.5 s (default: 0.5 s)
1)
1) Extension of the residual current transformer delay
Response to warning level
Here you can set how SIMOCODE pro should respond if the warning level is overshot.
See also "Tables of responses of SIMOCODE pro" in chapter Important information
(Page 7).
Table 4- 33 Response to "warning level" in ground-fault monitoring
0 to 25.5 s (default: 0.1 s)
1)
1) Extension of the residual current transformer delay