Parameters
4.3 Monitoring functions
SIMOCODE pro - Parameterize
134 Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
Here you can set the hysteresis for the ground-fault current:
0 to 15% of the level value in steps of 1%
5 %
Here you can set how SIMOCODE pro should respond to a sensor fault. Open circuit and
short-circuit to 3UL23 residual current transformer are recognized as sensor faults.