Parameters
4.1 Motor protection
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
45
Table 4- 2 Factors (linear) for trip times at operating temperature for 1st generation current / voltage
measuring modules
x I
s
Preload as a percentage of the current setting I
s
0
20
40
60
80
100
1.15
1
0.56
0.51
0.44
0.34
0.18
1.5
1
0.75
0.64
0.52
0.36
0.16
2
1
0.77
0.64
0.49
0.33
0.14
3
1
0.77
0.63
0.47
0.30
0.12
4
1
0.76
0.62
0.46
0.29
0.12
5
1
0.76
0.62
0.46
0.29
0.11
6
1
0.76
0.60
0.45
0.29
0.12
7.2
1
0.77
0.61
0.45
0.28
0.11
8
1
0.76
0.61
0.45
0.28
0.11
9
1
0.77
0.60
0.45
0.28
0.11
10
1
0.76
0.60
0.45
0.28
0.12
The following applies for the linear motor model:
When the rated motor current (I
s
) is at 100%, the value of "Thermal motor model" is
87% (1/1.15 x 100%) in a steady state, and 100% at the moment of an overload trip.
Example:
You have operated and switched off a motor with current setting 100% I
s
.
You immediately switch the motor back on. This causes an overload trip with 2 x I
s
, Class 10.
Tripping time in cold state: approximately 40 s (acc. to tripping characteristic)
Factor for tripping time with preload 100% I
s
: 0.19 (see Table)
Reduced tripping time: 0.19 x 40 s = 7.6 s.

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals