Parameters
4.1 Motor protection
SIMOCODE pro - Parameterize
46 Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
Pause time
The pause time is the specified time for the cooling down response of the motor when
tripped under normal operating conditions (not in the case of an overload trip). After this
interval, the thermal memory in SIMOCODE pro is erased and a new cold start is possible.
This means that many startups can be performed in a short space of time.
The following schematic shows the cooling down response with and without pause time:
Figure 4-6 Cooling down response with and without pause time
Note
Both the motor and the switching devices must be dimensioned
specifically for this load!
Pause time:
0 to 6553.5 s (default:. 0)