Parameters
4.2 Motor control
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
55
●
Control station - operator panel:
This control station is primarily intended for control
commands issued via the buttons on the 3UF72 operator panel, which is mounted in a
control cabinet door, for example. The plugs of the "Control Stations" function block must
be connected to any sockets (normally to the function block for the buttons of the
operator panel - OP buttons) for the control commands to take effect.
Note
Control functions with two speeds
Since the operator panel only has four buttons for controlling the motor feeder, one button
must be used as a speed changeover button for control functions with two speeds
and
two directions of rotation. For this purpose, this button must be assigned to the internal
control command "[OP]<>/<<>>".
Note
"Operator panel [OP]" control station
If the SIMOCODE
ES PC software on a programming device is connected to
pro via the system interface, its control commands automatically take effect
[OP]" control station. At the same time, the enabled commands
for this control station also take effect for SIMOCODE
ES.