3 Operation
3.3 Configuring Mode (Parameterization and Configuring Mode)
3.3.6 Configuring Mode FdEF (Define Functions)
Manual
152
SIP ART DR24 6DR2410
C79000-G7476-C153-03
3.3.6 Configuring Mode FdEF (Define Functions)
Functions required for the user program are defined in the configuring mode FdEF. The func-
tions (answer) are assigned to the initially empty” arithmetic blocks (question). They are as-
signed by setting question (arithmetic block) on dd2 and answer (function) on dd1 in pairs. Defi-
nition is effected on switching to the next question or returning to the configuring preselection
level after FdEF.
Every function assignment to the arithmetic blocks can be overwritten at any time in the confi-
guring mode FdEF or deleted with the assignment ndEF (not defined). The factory setting con-
tains ndEF for all arithmetic blocks.
The defined functions specify the scope of the other configuring modes AdAP, FCon, FPoS,
oFPA and CLPA and the scope of the parameterization mode onPA.
A distinction is made between basic functions and complex functions in the definition.
D Basic functions
109 arithmetic blocks b01.F to bh9.F with a max. 3 inputs and one output are available for
assignment with the 32 basic functions. The basic functions can be used as often as you like
and are offered in the answer cycle only for these arithmetic blocks.
D Complex functions
20 arithmetic blocks with different input/output formats are available for the assignment with
the 20 complex functions.
33 Arithmetic blocks
c01.F to c33.F with
4 inputs
1 output
for AFi1/2, Ain1 to 4, bin1 to 6, CPt1/2, dti1/2,
FUL1 to 3, FUP1/2
PUM 1 to 4, SPR1 to 8
4 Arithmetic blocks
d01. F to d04. F with
12 inputs
14 outputs
for CLoc, MUP1/2, Cnt1
4 Arithmetic blocks
h01. F to h04.F with
18 inputs
4 outputs
for Ccn1 to 4, CSE1 to 4, CSi1 to 4
The complex functions are offered in the answer cycle according to the different arithmetic
blocks and can be used as often as they are stored.

Table of Contents

Other manuals for Siemens SIPART DR24

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART DR24 and is the answer not in the manual?

Siemens SIPART DR24 Specifications

General IconGeneral
BrandSiemens
ModelSIPART DR24
CategoryController
LanguageEnglish

Related product manuals