3 Operation
3.3 Configuring Mode (Parameterization and Configuring Mode)
3.3.10Configuring Mode CAE4/CAE5 -- Setting UNI Module(s)
SIP ART DR24 6DR2410
C79000-G7476-C153-03
165
3.3.10.3 Measuring Range for Thermocouple with Internal Reference Point
(SEnS=tc.in)
D Set tc thermocouple type
D MA/ME range
Call parameters MA, ME, set range start and end according to the temperature unit (unit).
D CA/CE fine adjustment
Call parameter CA:
Set signal at the low end of the range, correct the display with CA if necessary.
Call parameter CE:
Set signal at the top end of the range, correct the display with CE if necessary.
3.3.10.4 Measuring Range for Thermocouple with External Reference Point
(SEnS=tc.EH)
D Set tc thermocouple type
D tb--external reference point temperature
Set the external reference point temperature with tb. Specify temperature unit with unit.
Attention: tb has no effect at tc=Lin
D MA/ME range
Call parameters MA, ME, set range start and end according to temperature unit (tc).
D CA/CE fine adjustment
Call parameter CA:
Set signal at the low end of the range, correct the display with CA if necessary.
Call parameter CE:
Set signal at the top end of the range, correct the display with CE if necessary.
3.3.10.5 Measuring Range for PT100--4--wire and PT100--3--wire Connection
(SEnS=Pt.3L/PT.4L)
D MA/ME range
Call parameters MA, ME, set range start and end:
-200 _C ≤ MA ≤ ME +850 _C
Specify temperature unit with Unit.
D CA/CE fine adjustment
Call parameter CA:
Set signal at the low end of the range, correct the display with CA if necessary.
Call parameter CE:
Set signal at the top end of the range, correct the display with CE if necessary.