2 Functions
122
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-37 Definition of current direction with transverse differential protection
The currents flow into the protected object even in case of healthy operation, in con-
trast to all other applications. For this reason, the polarity of one current transformer
set must be reversed, i.e. you must set a „wrong“ polarity, as described in Subsection
2.1.4 under „Current Transformer Data for 3-Phase Measuring Locations“.
Starpoint Condi-
tioning
If the differential protection is used as generator or motor protection, the starpoint con-
dition need not be considered even if the starpoint of the machine is earthed (high- or
low-resistant). The phase currents are always equal at both measuring points in case
of an external fault. With internal faults, the fault current results always in a differential
current.
Nevertheless, increased earth fault sensitivity can be achieved by the„Restricted Earth
Fault Protection“ (see section 2.3) or the „High-impedance Differential Protection“ (see
section 2.7) .
2.2.4 Differential Protection for Shunt Reactors
If current transformers are available for each phase at both sides of a shunt reactor,
the same considerations apply for series reactors.
In most cases, current transformers are installed in the lead phases and in the star-
point connection (see figure 2-38). In this case, comparison of the zero sequence cur-
rents is reasonable. The „Restricted Earth Fault Protection“ is most suitable for this ap-
plication (see 2.3).
If current transformers are installed in the line at both sides of the connection point of
the reactor (see figure 2-38), the same conditions as for auto-transformers apply. Such
an arrangement is therefore treated like an auto-transformer.
A neutral earthing reactor (starpoint former) outside the protected zone of a power
transformer can be treated as a separate protected object provided it is equipped with
current transformers like a shunt reactor. The difference is that the starpoint former
has a low impedance for zero sequence currents.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT63 series and is the answer not in the manual?

Siemens SIPROTEC 7UT63 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT63 series
CategoryProtection Device
LanguageEnglish

Related product manuals