4.2 Differential Protection
435
7UT613/63x Manual
C53000-G1176-C160-2
4.2 Differential Protection
Pickup Values
Time Delays
Figure 4-1 Tripping characteristic of the differential protection
I
diff
differential current = |I
1
+ I
2
|
I
rest
stabilising current = |I
1
| + |I
2
|
I
NObj
Nominal current of protected object
Differential current I
Diff
>/I
NObj
0.05 to 2.00 Steps 0.01
High-current stage I
Diff
>>/I
NObj
0.5 to 35.0
or ∞ (ineffective)
Steps 0.1
Increase of the pickup value when connect-
ing as a factor of I
Diff
>
1.0 to 2.0 Steps 0.1
Add-on restraint on external fault
(I
stab
> setting value)
Action time
I
Add-on
/I
NObj
2.00 to 15.00
2 to 250 cycles
or ∞ (active until dropout)
Steps 0.01
Increments 1 cycle
Trip characteristic see Figure 4-1
Tolerances (with preset characteristic parameters, for 2 sides with 1 measuring location each)
I
Diff
> stage and characteristic 5 % of set value
I
Diff
>> stage 5 % of set value
Delay of I
Diff
> stage T
IDiff>
0.00 s to 60.00 s
or ∞ (no trip)
Steps 0.01 s
Delay of I
Diff
>> stage T
IDiff>>
0.00 s to 60.00 s
or ∞ (no trip)
Steps 0.01 s
Time tolerance 1 % of set value or 10 ms
The set times are pure delay times

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT63 series and is the answer not in the manual?

Siemens SIPROTEC 7UT63 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT63 series
CategoryProtection Device
LanguageEnglish

Related product manuals