2.24 Command Processing
333
7UT613/63x Manual
C53000-G1176-C160-2
2.24.1.2 Sequence in the Command Path
Security mechanisms in the command path ensure that a switch command can be
carried out only if the test of previously established criteria has been successfully com-
pleted. Additionally, user-defined interlocking conditions can be configured separately
for each device. The actual execution of the command is also monitored after its re-
lease. The entire sequence of a command is described briefly in the following.
Checking a
Command Path
Please observe the following:
• Command entry, e.g. using the keypad on the local user interface of the device
– Check password → access rights;
– Check switching mode (interlocking activated/deactivated) → selection of deac-
tivated interlocking status.
• User configurable interlocking checks:
– Switching authority;
– Device position check (set vs. actual comparison);
– Zone controlled / bay interlocking (logic using CFC);
– System interlocking (centrally via SICAM);
– Double operation (interlocking against parallel switching operation);
– Protection blocking (blocking of switching operations by protection functions);
– Circuit breaker synchronization check (synchronism check before a close com-
mand).
• Fixed commands:
– Internal process time (software watch dog which checks the time for processing
the control action between initiation of the control and final close of the relay con-
tact);
– Configuration in process (if setting modification is in process, commands are re-
jected or delayed);
– Equipment present as output;
– Output block (if an output block has been programmed for the circuit breaker, and
is active at the moment the command is processed, then the command is reject-
ed);
– Component hardware malfunction;
– Command in progress (only one command can be processed at a time for each
circuit breaker or switch);
– 1–of–n check (for multiple allocations such as common contact relays or multiple
protection commands configured to the same contact it is checked if a command
procedure was already initiated for the output relays concerned or if a protection
command is present. Superimposed commands in the same switching direction
are tolerated).
Command Execu-
tion Monitoring
The following is monitored:
• Interruption of a command because of a cancel command,
• Running time monitor (feedback monitoring time).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT63 series and is the answer not in the manual?

Siemens SIPROTEC 7UT63 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT63 series
CategoryProtection Device
LanguageEnglish

Related product manuals