2.15 Overvoltage Protection
259
7UT613/63x Manual
C53000-G1176-C160-2
2.15 Overvoltage Protection
The overvoltage protection has the task of preventing from insulation problems by pro-
tecting electrical equipment against inadmissible abnormally high voltage levels.
High voltages occur in the power station sector, e.g. caused by incorrect manual op-
eration of the excitation system, faulty operation of the automatic voltage regulator,
(full) load shedding of a generator, separation of the generator from the system or
during island operation.
High voltages can also occur in the network by faulty operation of a voltage regulator
on the transformer or on longer weak load.
The overvoltage protection can only be used for three-phase protective objects. This
implies that the device is connected to a voltage transformer. This is therefore only
possible for 7UT613 and 7UT633. As the overvoltage protection only gets its measur-
ing information from the connected voltage measurement, it leaves the assignment of
currents to one side or a measuring location for the function without coating. Setting
causes the same differences as in other protection functions. If the overvoltage pro-
tection is assigned to one side of the main protective object or the three-phase busbar,
the voltage limits in related values (U/UN) have to be set. The values are set to sec-
ondary in volts when assigned to a measuring location.
2.15.1 Function Description
The overvoltage protection assesses the largest of the three phase-to-phase voltages
or the highest of the three phase-to-earth voltages (adjustable).
Overvoltage protection includes two stages. In case of a high overvoltage, the
switchoff is performed with a short-time delay, whereas in case of lower overvoltages,
the switchoff is performed with a longer time delay. Voltage limit values and delay
times can be set individually for both stages.
Furthermore, the entire overvoltage protection can be blocked vie a binary input.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT63 series and is the answer not in the manual?

Siemens SIPROTEC 7UT63 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT63 series
CategoryProtection Device
LanguageEnglish

Related product manuals