4 Technical Data
472
7UT613/63x Manual
C53000-G1176-C160-2
4.13 Forward active power supervision
Setting Ranges / Increments
Times
Dropout Ratios
Tolerances
Forward power P
forward
< 1.7 W up to 3000.0 W
0.01 P/SnS up to
17.00 P/SnS
Increment 0.1 W
Increment 0.1 W
Forward power P
forward
> 1.7 W up to 3000.0 W
0.01 P/SnS up to
17.00 P/SnS
Increment 0.1 W
Increment 0.1 W
Delay Times T 0,00 s to 60.00 s
or ∞ (disabled)
Increments 0.01 s
Pickup times
- Active power P<, P>
with high–accuracy measurement:
approx. 330 ms at f = 50 Hz
approx. 310 ms at f = 60 Hz
approx. 970 ms at f = 16.7 Hz
with high-speed measurement:
approx. 30 ms at f = 50 Hz
approx. 30 ms at f = 60 Hz
approx. 70 ms at f = 16.7 Hz
Dropout times
- active power P<, P>
with high–accuracy measurement:
approx. 330 ms at f = 50 Hz
approx. 310 ms at f = 60 Hz
approx. 970 ms at f = 16.7 Hz
with high-speed measurement:
approx. 30 ms at f = 50 Hz
approx. 30 ms at f = 60 Hz
approx. 70 ms at f = 16.7 Hz
Active power P
Act
< approx. 1.10 or 0.5 % of S
N
Active power P
Act
> approx. 0.90 or 0.5 % of S
N
Active power P<, P> 0.25 % S
N
±3 % of setting value
with high-accuracy measurement
0.5 % S
N
±3 % of setting value
with high-speed measurement
(S
N
: Rated apparent power)
Delay Times T 1 % or 10 ms

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT63 series and is the answer not in the manual?

Siemens SIPROTEC 7UT63 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT63 series
CategoryProtection Device
LanguageEnglish

Related product manuals