4.18 External Trip Commands
479
7UT613/63x Manual
C53000-G1176-C160-2
4.18 External Trip Commands
Binary Inputs for Direct Tripping
Transformer Annunciations
Number 2
Operating Time approx. 12.5 ms min.
approx. 25 ms typical
Dropout time approx. 25 ms
Delay time 0.00 s to 60.00 s Steps 0.01 s
Time tolerance 1 % of set value or 10 ms
The set times are pure delay times.
External annunciations Buchholz warning
Buchholz tank
Buchholz tripping