2 Functions
178
7UT613/63x Manual
C53000-G1176-C160-2
2.4.3.3 Information List
2321 3I0p 1A 0.05 .. 4.00 A 1.00 A 3I0p Pickup
5A 0.25 .. 20.00 A 5.00 A
2322 3I0p 0.05 .. 4.00 I/InS 1.00 I/InS 3I0p Pickup
2323 T 3I0p 0.05 .. 3.20 sec; ∞ 0.50 sec T 3I0p Time Dial
2324 D 3I0p 0.50 .. 15.00 ; ∞ 5.00 D 3I0p Time Dial
No. Information Type of In-
formation
Comments
191.2404 >BLK 3I0 O/C SP >BLOCK 3I0 time overcurrent
191.2411 O/C 3I0 OFF OUT Time Overcurrent 3I0 is OFF
191.2412 O/C 3I0 BLK OUT Time Overcurrent 3I0 is BLOCKED
191.2413 O/C 3I0 ACTIVE OUT Time Overcurrent 3I0 is ACTIVE
191.2425 O/C 3I0 PU OUT Time Overcurrent 3I0 picked up
191.2491 O/C 3I0 Not av. OUT O/C 3I0: Not available for this object
191.2501 >BLK 3I0O/C Inr SP >BLOCK time overcurrent 3I0 InRush
191.2502 >BLOCK 3I0>> SP >BLOCK 3I0>> time overcurrent
191.2503 >BLOCK 3I0> SP >BLOCK 3I0> time overcurrent
191.2504 >BLOCK 3I0p SP >BLOCK 3I0p time overcurrent
191.2514 3I0>> BLOCKED OUT 3I0>> BLOCKED
191.2515 3I0> BLOCKED OUT 3I0> BLOCKED
191.2516 3I0p BLOCKED OUT 3I0p BLOCKED
191.2521 3I0>> picked up OUT 3I0>> picked up
191.2522 3I0> picked up OUT 3I0> picked up
191.2523 3I0p picked up OUT 3I0p picked up
191.2524 3I0> InRush PU OUT 3I0> InRush picked up
191.2525 3I0p InRush PU OUT 3I0p InRush picked up
191.2529 3I0 InRush PU OUT 3I0 InRush picked up
191.2541 3I0>> Time Out OUT 3I0>> Time Out
191.2542 3I0> Time Out OUT 3I0> Time Out
191.2543 3I0p TimeOut OUT 3I0p Time Out
191.2551 3I0>> TRIP OUT 3I0>> TRIP
191.2552 3I0> TRIP OUT 3I0> TRIP
191.2553 3I0p TRIP OUT 3I0p TRIP
Addr. Parameter C Setting Options Default Setting Comments