3.3 Commissioning
411
7UT613/63x Manual
C53000-G1176-C160-2
The phase angles must be 180° in all cases.
Check the differential and restraint currents for each phase.
If single-phase primary checks cannot be carried out but only symmetrical operational
currents are available, polarity or connecting errors in the earth current path with sum-
mation transformer connection L1–L3–E will not be detected with the before-men-
tioned checks. In this case, asymmetry is to be achieved by secondary manipulation.
Therefore the current transformer of phase L2 is short-circuited as shown in figure
3-39.
DANGER!
Manipulations on the measuring current transformers must be performed with
the utmost precaution!
Non-observance of the following measures will result in death, severe personal injury
or substantial property damage.
Short-circuit the current transformers before disconnecting any current supply leads
to the device!
Figure 3-39 Asymmetrical test with summation transformer connection L1-L3-E
The measured current is now 2.65 times the current of the symmetrical test.
This test must be carried out for each summation CT.
3.3.11 Testing of the Non-Assigned 1-Phase Current Inputs
As far as single-phase current inputs belong to the main protected object, i.e. they are
assigned to a side of the main protected object, they were already checked with the
zero sequence current tests.
Even if they are not assigned to the main protected object but to a 3-phase measuring
location of a further protected object (e.g. restricted earth fault protection for a sepa-
rate neutral earthing reactor), the same procedure as for the zero sequence current
applies. Perform the zero sequence current tests unless it has already been done.
Single-phase measured current inputs of the device can also be used for any desired
1-phase protection function. If this is an actual case and the same input has not yet

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT63 series and is the answer not in the manual?

Siemens SIPROTEC 7UT63 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT63 series
CategoryProtection Device
LanguageEnglish

Related product manuals