4.21 Flexible Protection Functions
485
7UT613/63x Manual
C53000-G1176-C160-2
4.21 Flexible Protection Functions
Measured Values / Operating Modes
Setting Range / Increments
Measured values I-measuring point / I-side
I1 .. I12 (for busbar 1-ph.)
IZ1 .. IZ4
U, P, Q, cos Ï•, f
Measuring procedure for I-measuring
point / I-sides / U
Evaluation of only one phase,
fundamental component,
positive sequence system,
negative sequence system,
zero sequence system
Pickup when threshold is exceeded,
when below threshold
Pickup thresholds
Current I-measur-
ing point
for I
N
= 1 A 0.05 to 35.00 A Increment 0.01 A
for I
N
= 5 A 0.25 to 175.00 A
Current I-side 0.05 to 35.00 I
N
Increment 0.01 I
N
Current I1 .. I12 for I
N
= 1 A 0.05 to 35.00 A Increment 0.01 A
for I
N
= 5 A 0.25 to 175.00 A
for I
N
= 0.1 A 0.005 to 3.500 A Increment 0.001 A
Current IZ1 .. IZ4 for I
N
= 1 A 0.05 to 35.00 A Increment 0.01 A
for I
N
= 5 A 0.25 to 175.00 A
Current IZ3, .IZ4 for sensitive CT 0.001 to 1.500 A Increment 0.001 A
Voltage U, U4 1.0 to 170.0 V Increment 0.1 V
Power P for I
N
(meas. pt) = 1 A 1.7 to 3000.0 W Increment 0.1 W
for I
N
(meas. pt) = 5 A 8.5 to 15,000.0 W
for side 0.01 to 17.00 P/SnS Increment 0.01
P/SnS
Power Q for I
N
(meas. pt) = 1 A 1.7 to 3000.0 VAR Increment 0.1 VAR
for I
N
(meas. pt) = 5 A 8.5 to 15,000.0 VAR
for side 0.01 to 17.00 Q/SnS Increment 0.01
Q/SnS
Power factor cos Ï• -0.99 to 0.99 Increment 0.01
Frequency for f
N
= 50 / 60 Hz
40.00 to 66.00 Hz Increment 0.01 Hz
for f
N
= 16.7 Hz
10.00 to 22.00 Hz
Dropout ratio >-stage except for cos Ï•, f 0.70 to 0.99 Increment 0.01
Dropout ratio <-stage except for cos Ï•, f 1.01 to 3.00
Dropout difference for cos Ï• 0,015
Dropout difference for f 0.02 Hz
Trigger delay 0.00 to 60.00 s Increment 0.01 s
Command time delay 0.00.3600.00 s
Dropout delay 0.00 to 60.00 s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT63 series and is the answer not in the manual?

Siemens SIPROTEC 7UT63 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT63 series
CategoryProtection Device
LanguageEnglish

Related product manuals