4 Technical Data
478
7UT613/63x Manual
C53000-G1176-C160-2
4.17 Circuit Breaker Failure Protection
Circuit Breaker Supervision
Starting Conditions
Times
Current flow monitoring 0.04 A to 1.00 A
1)
for the respective side
Steps 0.01 A
Dropout-to-pickup ratio approx. 0.9 for I ≥ 0.25 A
1)
Tolerance 5 % of set value or 0.01 A
1)
Breaker status monitoring via circuit breaker auxiliary contacts and
binary input
1)
Secondary values based on I
N
= 1 A; for I
N
= 5 A the currents must be multiplied by 5.
For breaker failure protection internal trip
external trip (via binary input)
Pickup time for f
N
= 50 / 60 Hz approx. 3 ms with measured quantities,
approx. 20 ms after switch-on of measured
quantities
Pickup time for f
N
= 16.7 Hz approx. 60 ms after switch-on of measured
quantities
Dropout time for f
N
= 50/60 Hz approx. 25 ms
Dropout time for f
N
= 16.7 Hz approx. 75 ms
Times 0.00 s to 60.00 s; ∞ Steps 0.01
Time tolerance 1 % of set value or 10 ms

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT63 series and is the answer not in the manual?

Siemens SIPROTEC 7UT63 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT63 series
CategoryProtection Device
LanguageEnglish

Related product manuals