2 Functions
266
7UT613/63x Manual
C53000-G1176-C160-2
The following example illustrates a setting of the frequency protection for a generator
that indicates a delayed warning at approx. 1 % decreased frequency. In case of a
further frequency decrease, the generator is disconnected from the network and finally
shut down.
Minimum Voltage The frequency protection is blocked on undershooting the minimum voltage U MIN.
The recommended value is approx. 65 % U
N
. The setting value is based on phase-
phase voltages. If the frequency protection of one side of the main protected object,
the value must be set as reference value under address 5652 U MIN, e.g. 0.65. When
assigned to a measuring location the value of phase-phase voltage must be set under
address 5651 Umin in Volt , e.g. 71. V at U
N sec
= 110 V (65 % of 110 V). The
minimum voltage threshold can be deactivated by setting this address to 0. However,
no frequency measuring is possible below approx. 5 V (secondary) so that the fre-
quency protection can no longer function.
2.16.3 Settings
Level
Changes to
CPU modules
Setting at f
N
=
Delay
50 Hz 60 Hz 16.7 Hz
f< Warning 49.50 Hz 59.50 Hz 16.60 Hz 20.00 s
f<<
Disconnection
from the network
48.00 Hz 58.00 Hz 16.00 Hz 1.00 s
f<<< Shutdown 47.00 Hz 57.00 Hz 15.70 Hz 6.00 s
f> Warning and trip 52.00 Hz 62.00 Hz 17.40 Hz 10.00 s
Addr. Parameter Setting Options Default Setting Comments
5601 O/U FREQUENCY OFF
ON
Block relay
OFF Over / Under Frequency Protec-
tion
5611 f< 40.00 .. 49.99 Hz; 0 49.50 Hz Pick-up frequency f<
5612 f<< 40.00 .. 49.99 Hz; 0 48.00 Hz Pick-up frequency f<<
5613 f<<< 40.00 .. 49.99 Hz; 0 47.00 Hz Pick-up frequency f<<<
5614 f> 50.01 .. 66.00 Hz; ∞ 52.00 Hz Pick-up frequency f>
5621 f< 50.00 .. 59.99 Hz; 0 59.50 Hz Pick-up frequency f<
5622 f<< 50.00 .. 59.99 Hz; 0 58.00 Hz Pick-up frequency f<<
5623 f<<< 50.00 .. 59.99 Hz; 0 57.00 Hz Pick-up frequency f<<<
5624 f> 60.01 .. 66.00 Hz; ∞ 62.00 Hz Pick-up frequency f>
5631 f< 10.00 .. 16.69 Hz; 0 16.50 Hz Pick-up frequency f<
5632 f<< 10.00 .. 16.69 Hz; 0 16.00 Hz Pick-up frequency f<<
5633 f<<< 10.00 .. 16.69 Hz; 0 15.70 Hz Pick-up frequency f<<<
5634 f> 16.67 .. 22.00 Hz; ∞ 17.40 Hz Pick-up frequency f>
5641 T f< 0.00 .. 100.00 sec; ∞ 20.00 sec Delay time T f<
5642 T f<< 0.00 .. 600.00 sec; ∞ 1.00 sec Delay time T f<<
5643 T f<<< 0.00 .. 100.00 sec; ∞ 6.00 sec Delay time T f<<<

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT63 series and is the answer not in the manual?

Siemens SIPROTEC 7UT63 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT63 series
CategoryProtection Device
LanguageEnglish

Related product manuals