2.4 Time Overcurrent Protection for Phase and Residual Currents
177
7UT613/63x Manual
C53000-G1176-C160-2
2211 3I0>> 1A 0.05 .. 35.00 A; ∞ 1.00 A 3I0>> Pickup
5A 0.25 .. 175.00 A; ∞ 5.00 A
2212 3I0>> 0.05 .. 35.00 I/InS; ∞ 1.00 I/InS 3I0>> Pickup
2213 T 3I0>> 0.00 .. 60.00 sec; ∞ 1.50 sec T 3I0>> Time Delay
2214 3I0> 1A 0.05 .. 35.00 A; ∞ 0.40 A 3I0> Pickup
5A 0.25 .. 175.00 A; ∞ 2.00 A
2215 3I0> 0.05 .. 35.00 I/InS; ∞ 0.40 I/InS 3I0> Pickup
2216 T 3I0> 0.00 .. 60.00 sec; ∞ 2.00 sec T 3I0> Time Delay
2221 3I0p 1A 0.05 .. 4.00 A 0.40 A 3I0p Pickup
5A 0.25 .. 20.00 A 2.00 A
2222 3I0p 0.05 .. 4.00 I/InS 0.40 I/InS 3I0p Pickup
2223 T 3I0p 0.05 .. 3.20 sec; ∞ 0.50 sec T 3I0p Time Dial
2224 D 3I0p 0.50 .. 15.00 ; ∞ 5.00 D 3I0p Time Dial
2225 TOC DROP-OUT Instantaneous
Disk Emulation
Disk Emulation TOC Drop-out Characteristic
2226 IEC CURVE Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
2227 ANSI CURVE Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse ANSI Curve
2231 I/I0p PU T/TI0p 1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
Pickup Curve 3I0/3I0p - T3I0/T3I0p
2232 MofPU ResT/TI0p 0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
Multiple of Pickup <-> T3I0/T3I0p
2241 2.HARM. 3I0 10 .. 45 % 15 % 2nd harmonic O/C 3I0 in % of fundamental
2242 I Max InRr. 3I0 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inr. Rest. O/C 3I0
5A 1.50 .. 125.00 A 37.50 A
2243 I Max InRr. 3I0 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest. O/C 3I0
2311 3I0>> 1A 0.05 .. 35.00 A; ∞ 7.00 A 3I0>> Pickup
5A 0.25 .. 175.00 A; ∞ 35.00 A
2312 3I0>> 0.05 .. 35.00 I/InS; ∞ 7.00 I/InS 3I0>> Pickup
2313 T 3I0>> 0.00 .. 60.00 sec; ∞ 1.50 sec T 3I0>> Time Delay
2314 3I0> 1A 0.05 .. 35.00 A; ∞ 1.50 A 3I0> Pickup
5A 0.25 .. 175.00 A; ∞ 7.50 A
2315 3I0> 0.05 .. 35.00 I/InS; ∞ 1.50 I/InS 3I0> Pickup
2316 T 3I0> 0.00 .. 60.00 sec; ∞ 2.00 sec T 3I0> Time Delay
Addr. Parameter C Setting Options Default Setting Comments