7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 39
mmmmm
A: Technical Reference
Open Channel Monitoring (OCM)
OCM converts a level reading (head) into a flow value using a linear algorithm.
SITRANS Probe LU can convert a head level measurement into a flow rate, using an
eleven breakpoint head-versus-flow characteristic curve. This chart is usually available
from the manufacturer of the v-notch weir, Parshall flume, or other open channel device.
Linearization type must be set to Linearization Table, and up to 32 breakpoints must be set
for head levels and corresponding flowrates (using the Volume tables). Once these
breakpoints are set, the output is scaled to represent the flowrate, and the RUN mode
display will show the flowrate.
Example: Flow Characterization (using 11 breakpoints)
The maximum and minimum points on the curve must be defined. Then program the
remaining breakpoints to closely match the flow curve of your open channel device.
Chemical compatibility
The plastic materials used in the construction of SITRANS Probe LU (ETFE, PBT, PEI, and
PVDF) are resistant to attack from most chemicals. For exposure to specific
environments, check with chemical compatibility charts before installing and operating
SITRANS Probe LU in your application.
11
10
9
8
7
6
5
4
3
2
1
12 3 4 65789
10
11
head (level) breakpoints
flow (volume) breakpoints

Table of Contents

Other manuals for Siemens sitrans PROBE LU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens sitrans PROBE LU and is the answer not in the manual?

Siemens sitrans PROBE LU Specifications

General IconGeneral
Measuring PrincipleUltrasonic
CommunicationHART
Output4 to 20 mA
Power Supply12 to 30 V DC
Process Temperature-40 to 80 °C
Enclosure RatingIP68
MaterialPVDF
Ambient Temperature-40 to 70 °C
Measurement Range0.25 to 12 m (0.8 to 39 ft)

Related product manuals