ALC700 Series Light Tower Set Controller
ALC700 Series Light Tower Set Controller 2018-03-02 Version 1.4 Page 21 of 51
5.7 REMOTE START MODE
A. Set arbitrary input port as “Remote Start”. Press ,its indicator light on, and controller
enters Auto Mode. Meanwhile, the panel display Auto Mode Select (Fig 1); Press and
to select 04 REMOTE START and press or to confirm (Fig 2).
B. When remote start input port is active (input port can be set via utility computer software),
remote start delay begins and audible alarm relay is active (if configured). When remote
start delay is over and remote start signal is active, light tower set begin cranking and
flashlight is twinkling (if configured). (Fig 3, 4).
C. If generator voltage and frequency has reached on-load requirements (Voltage ≥ on-load
voltage and frequency ≥ on-load frequency), all the lights will illuminate in proper order and
the illumination interval delay is 2s (can be set as 1~300s). (Fig 5)