ALC700 Series Light Tower Set Controller
ALC700 Series Light Tower Set Controller 2018-03-02 Version 1.4 Page 27 of 51
6.2 SHUTDOWN ALARMS
When controller detects shutdown alarm, it will send signal to turn off #1~#8 lights and shuts
down generator.
Shutdown alarms as following:
When controller detects emergency stop signal, it will send a
shutdown signal and the corresponding alarm information will
be displayed on the LCD.
When controller detects the temperature is higher than the set
value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
When controller detects the oil pressure is lower than the set
value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
When controller detects the generator speed is higher than the
set value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
When controller detects the generator speed is lower than the
set value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
When controller detects the generator speed is 0, it will send a
shutdown signal and the corresponding alarm information will
be displayed on the LCD.
When controller detects the generator frequency is higher than
the set value, it will send a shutdown signal and the
corresponding alarm information will be displayed on the LCD.
When controller detects the generator frequency is lower than
the set value, it will send a shutdown signal and the
corresponding alarm information will be displayed on the LCD.
When controller detects the generator voltage is higher than
the set value, it will send a shutdown signal and the
corresponding alarm information will be displayed on the LCD.
When controller detects the generator voltage is lower than the
set value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
When controller detects the current is higher than the set
value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
If genset start failure within setting of start times, it will send a
shutdown signal and the corresponding alarm information will
be displayed on the LCD.