- 109 -
No.SFOD-OMT0010-B
Required
speed is
not
achieved
Check that the parameter values are
correct.
Review the maximum speed and the
maximum acceleration and deceleration of
the actuator.
Correct the parameter values and test the
operation.
-> 7. Settings Data Entry
Operation
pattern is
not suitable.
Check if a triangular acceleration /
deceleration is programmed for the
actuator operation. In case of such
operation, the actuator may start slowing
down before it reaches the maximum
speed.
Modify the setting to make the movement
distance longer or the acceleration higher.
-> 7. Settings Data Entry
Check that the controller parameter
settings for the product model and power
supply specification are appropriate for the
actuator connected.
Check that the controller parameters for the
product number of the actuator matches the
actuator connected. Check that the power
supply specification is correct.
-> 4. Product Specifications
Check for a temporary voltage drop in the
power supply? (If there is a temporary
voltage drop in the power supply, the EMG
terminal of the motor control power
connector will turn OFF, so the actuator will
stop. However, this stop will be released
when the voltage recovers).
There is a possibility of a momentary voltage
drop because the capacity of the power supply
is insufficient, or if the power supply is an
“inrush-current protection” type.
-> 4. Product Specifications