Safety
Warning!
· If an external residual current device (RCD) (type A is recommended) is
mandatory, the switch must be triggered at a residual current of 300 mA
(recommended). RCD of other specifcations can also be used according to
local standard.
Ø PE Connection and Leakage Current
• All inverters incorporate a certified internal Residual Current Monitoring
(RCM) in order to protect against possible electrocution and fire hazard
in case of a malfunction in the PV array, cables or inverter.
There are 2 trip thresholds for the RCM as required for certification
(IEC 62109-2:2011).
The default value for electrocution protection is 30 mA, and for slow
rising current is 300 mA.
The islanding effect means that when the power grid is cut off, the
grid-connected power generation system fails to detect the power
outage and still supplies power to the power grid. This is very dangerous
for the maintenance personnel and the power grid on the transmission
line.
This inverter use active frequency offset method to prevent islanding
effect.
Ø Anti-lslanding Effect
High leakage Current!
Earth connection essential before connecting supply.
• A faulty ground connection can result in equipment failure, personal
and death injuries, and electromagnetic interference.
• Ensure correct according to grounding to IEC62109 and conductor
diameter according to STANDARD specification.
• Do not connect the grounding end of the equipment in series to
prevent multi-point grounding.
• Electrical appliances must be installed in accordance with the wiring
rules of each country.
This inverter should pair with high voltage battery, for the specifc
parameters such as battery type, nominal voltage and nominal capacity
etc., please refer to section 4.3.
Please refer to the matching battery specifcation for details.
Ø Battery Safety Instructions
For United Kingdom
The installation that connects the equipment to the supply terminals
shall comply with the requirements of BS 7671.
• Electrical installation of PV system shall comply with requirements of
BS 7671 and IEC 60364-7-712.
• All protective devices cannot be changed.
• User shall ensure that equipment is so installed, designed and
operated to maintain at all times compliance with the requirements of
ESQCR22(1)(a).

Other manuals for SolaX Power X1 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SolaX Power X1 Series and is the answer not in the manual?

SolaX Power X1 Series Specifications

General IconGeneral
BrandSolaX Power
ModelX1 Series
CategoryInverter
LanguageEnglish

Related product manuals