7 LCD Operation User Manual
60
Grid Protection Voltage Adjusting
All SUNGROW inverters are compliant with the local standard related to grid
protection requirements. In order to work with unstable utility grid, inverters are
equipped with automatic protection voltage adjusting function (disabled by
default). This mode can be enabled via the LCD.
OFF (default setting): the function is disabled. The grid protection voltage
cannot automatically adjust.
ON: enables the protection function. The inverter will automatically adjust the
protection threshold to a higher value so as to be normally connected to the grid
in the event of grid over-voltage. The V
max-rec
will be adjusted the same with the
V
max
, with an upper limit value not higher than V
max
.
If the setting is changed from ON to OFF, you must
set the protection voltage as specified in Tab. 7-3
according to local protection requirements.
OFF ON Esc
7.5.3 Total Export Setting
Touch to select and touch ENT to confirm.
Touch to change the value and touch ENT to move the cursor.
Touch to select Enter and touch ENT to confirm settings.
OFF (default setting): all power will be fed into the
utility grid.
ON: no power will be fed into the utility grid.
Total Export: maximum feed-in power limit for the
PV system.
ONOFF
Total Export: 1000W
Esc
Enter Esc
ON:
A prompt will appear when you set it for the second
time.
Set by solar
professionals only

Table of Contents

Other manuals for Sungrow SG2K5-S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG2K5-S and is the answer not in the manual?

Sungrow SG2K5-S Specifications

General IconGeneral
BrandSungrow
ModelSG2K5-S
CategoryInverter
LanguageEnglish

Related product manuals