User Manual 10 Operation of LCD Display
77
Parameter Description Default Range
PF
Inverter output power
factor
+1.000
-1.000~-0.80
0/
+0.800~+1.0
00
Q-Var limits
Inverter reactive power
limitation
0.0%
0~+100%/
0~-100%
Time
param
Standby time
Time from inverter
standby to startup
20s 20~255s
Recover time
Time from inverter fault
is removed to standby
30s
[IT: 300s]
0-900s
LVRT param
Set the LVRT to OFF or
ON. When it is ON,
inverter can keep
grid-connection for a
certain time when grid
fault occurs and provide
reactive power for grid
recovery.
[OFF] [OFF]/ [ON]
Derating param
Set the Derating param
to OFF or ON. If it is ON,
inverter will operate
with power derating
when grid frequency
exceeds the set value.
[OFF] [OFF]/ [ON]
Iso
param
ISO
Set the ISO protection
function to ON or OFF.
When it is ON, inverter
will not connect to the
grid when resistance to
the ground is below the
set value.
[ON] [OFF]/ [ON]
ISO pro value
Set the resistance to the
ground.
30KΩ 20~3000K
10.10.2 Active/Reactive Power Parameters
Main Screen (Press ENTER)Menu (Press ×3)Set-param (Press ENTER)
Enter password (Press ENTER, Press )Run-param (Press ENTER) P-Q Param
(Press ENTER)

Table of Contents

Other manuals for Sungrow SG50KTL-M-20

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG50KTL-M-20 and is the answer not in the manual?

Sungrow SG50KTL-M-20 Specifications

General IconGeneral
BrandSungrow
ModelSG50KTL-M-20
CategoryInverter
LanguageEnglish

Related product manuals