166 CG-SVX17D-EN
Maintenance
Pump Package Motor Lifting
20-70 Ton — Slant, V Frame Units
• Attach block and tackle to lifting bracket which is attached to condenser from directly above
pump package, shown in Figure 100, p. 166.
• Attach lifting cables around pump motor, or to pump motor hooks, where available.
80-130 Ton — W Frame Units
• Remove louvered panels and center condenser box frame vertical support as shown in
Figure 101, p. 167.
• Attach block and tackle to 3/8” x 16 lifting eyebolt which is located in the top of the condenser
box as shown in
Figure 101, p. 167.
• Motor and pump must be separated and removed through opening created by removal of
loubered panels and vertical support.
• Attach lifting cables to motor hooks to remove.
Figure 100.Pump lifting bracket—20-70 ton — Slant, V Frame