72 CG-SVX17D-EN
Installation - Electrical
General Recommendations
All wiring must comply with local codes and the National Electric Code. Typical field wiring
diagrams are included at the end of the manual. Minimum circuit ampacities and other unit
electrical data are on the unit nameplate. See the unit order specifications for actual electrical data.
Specific electrical schematics and connection diagrams are shipped with the unit.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
CAUTION
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper
conductors may result in equipment damage.
NOTICE:
Isolate Conduits!
Do not allow conduit to interfere with other components, structural members or equipment.
Control voltage (115V) wiring in conduit must be separate from conduit carrying low voltage
(<30V) wiring. To prevent control malfunctions, do not run low voltage wiring (<30V) in conduit
with conductors carrying more than 30 volts.