16 CG-SVX17D-EN
General Data
General Data
Table 1. General Data - 60 Hz - IP
Size 20 26 30 35 40 52 60 70 80 90 100 110 120 130
Compressor
Number# 2 2224444444446
Tonnage/circuit¹ 10+10 13+13 15+15 15+20 10+10 13+13 15+15 15+20 20+20 20+25 25+25 25+30 30+30
20+20
+25
Evaporator
Water storage (gal) 1.4 2.2 2.2 3.2 2.4 4.1 5.0 7.5 7.0 9.0 10.3 11.5 11.5 12.3
Min. flow² (gpm) 24 30 34 40 46 59 68 80 92 103 116 126 136 147
Max. flow² (gpm) 69 89 100 117 136 176 201 238 275 307 346 375 407 440
Water connection(in)22.52.52.53333444444
Pump Package
Avail head pressure (ft H2O) 80.1 79.1 72.8 70.5 67.1 59.0 78.7 66.4 63.2 59.3 71.9 65.0 75.7 63.9
Power (HP) 5.0 5.0 5.0 5.0 5.0 5.0 7.6 7.6 10.2 10.2 10.2 10.2 15.2 15.2
Expansion tank
volume
(gal)55555555666666
Buffer Tank
Buffer tank volume (gal) 140 140 140 140 140 140 140 140 152 152 195 195 195 195
Condenser
Quantity of coils# 1 1112222444444
Coil length (in) 91 91 127 127 91 91 127 127 121 121 144 144 144 180
Coil height (in) 68 68 68 68 68 68 68 68 42 42 42 42 42 42
Number of rows# 2 2222222333333
Fins per foot (fpf) 192 192 192 192 192 192 192 192 192 192 192 192 192 192
Fan
Quantity# 2 23344666688810
Diameter (in) 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8 28.8
Airflow per fan (cfm) 9413 9420 9168 9173 9413 9420 9168 9173 9470 9472 9094 9096 9098 9094
Power per motor (kW) 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
Motor RPM (rpm) 840 840 840 840 840 840 840 840 840 840 840 840 840 840
Tip speed (ft/min) 6333 6333 6333 6333 6333 6333 6333 6333 6333 6333 6333 6333 6333 6333
General Unit
Refrig circuits# 1 1112222222222
Capacity steps % 50-100 50-100 50-100 43-100
25-50-
75-100
25-50-
75-100
25-50-
75-100
21-43-
71-100
25-50-
75-100
22-44-
72-100
25-50-
75-100
23-45-
73-100
25-50-
75-100
15-31-
46-62-
81-100
Refrig charge/
circuit ¹
(lbs)32 344848323250.54874789091.586112
Oil charge/circuit¹ (gal) 1.7 1.7 3.5 3.5 1.7 1.7 3.5 3.5 3.5 3.5 3.5 3.7 3.8 5.8
Min ambient(°F)00000000000000
1. Data shown for circuit one only. The second circuits always matches.
2. Flow limits are for water only.