170 CG-SVX17D-EN
Diagnostics
Very Low Suction Pressure – Circuit 2
Very Low Suction Pressure – Circuit 2
Very Low Suct Press – Ckt 2
Chiller Immediate Latch
All
[circuit in manual
lockout]
The circuit’s suction pressure dropped
below (Low Pressure Cutout Setpoint
(kPa absolute) * 0.5)
regardless of whether or not
compressors are running on that
circuit. This diagnostic was created to
prevent compressor failures due to
crossbinding by forcing an entire chiller
shutdown. If a given circuit is locked
out, the suction pressure transducer
associated with it will be excluded from
causing this diagnostic.
Local
High Discharge Temperature
High Discharge Temperature
High Discharge Temperature
Circuit Immediate NonLatch
Ckt Energized
[Ckt Not
Energized]
The discharge temperature exceeded
the limits for the compressor.
Local
High Discharge Temperature Lockout
High Discharge Temperature Lockout
High Discharge Temp Lockout
Circuit Immediate Latch All
High discharge temperature
diagnostics occurred over 210
minutes.
Compressor Fault
Compressor Fault
Compressor Fault
Cprsr Immediate NonLatch All
The compressor fault switch input is
open. See Table 64, p. 158 for CSHN
compressor protection module
diagnostics indicators.
Local
Compressor Fault Lockout
Compressor Fault Lockout
Compressor Fault Lockout
Cprsr Immediate Latch All
The compressor fault switch input
remained open for more than 35
minutes.
Five compressor fault diagnostics have
occurred within the last 210 minutes.
Local
BAS Failed to Establish
Communication
BAS Failed to Establish
Communication
BAS Failed to Establish Comm
Chiller Special NonLatch At power-up
The BAS was setup as “installed” and
the BAS did not communicate with the
MP within 15 minutes after power-up.
Remote
BAS Communication Lost
BAS Communication Lost
BAS Communication Lost
Chiller Special NonLatch All
The BAS was setup as “installed” at the
MP and the LCI-C LLID lost
communications with the BAS for 15
continuous minutes after it had been
established.
Remote
LCI-C Software Mismatch: Use BAS
Tool
LCI-C Software Mismatch: Use BAS
Tool
LCI-C Software: Use BAS Tool
Chiller Warning NonLatch All
LCI-C Neuron software and LCI-C IPC3
software do not match. Load new LCI-
C Neuron software using LonTalk
service tool.
Remote
External Chilled/Hot Water Setpoint
External Chilled/Hot Water Setpoint
Ext Chilled/Hot Water Setpt
Chiller Warning NonLatch All
a. Function Not “Enabled”: no
diagnostics. B. “Enabled “: Out-Of-
Range Low or Hi or bad LLID, set
diagnostic, default CWS/HWS to next
level of priority (e.g. Front Panel
SetPoint). This Warning diagnostic will
automatically reset if the input returns
to the normal range.
Remote
External Demand Limit Setpoint
External Demand Limit Setpoint
External Demand Limit Setpt
Chiller Warning NonLatch All
a. Function Not “Enabled”: no
diagnostics. B. “Enabled “: Out-Of-
Range Low or Hi or bad LLID, set
diagnostic, default DLS to next level of
priority (e.g. Front Panel SetPoint).
This Warning diagnostic will
automatically reset if the input returns
to the normal range.
Remote
Circuit Pumpdown Terminated
Circuit Pumpdown Terminated
Circuit Pumpdown Terminated
Circuit Warning Latching
Operational/
Service
Pumpdown [All
Except
Operational and
Service
Pumpdown]
The procedure did not terminate
normally by reaching the termination
pressure within the allotted time.
See “Compressor Operational Pump
Down,” p. 159 or “Compressor Service
Pump Down Procedure,” p. 159.