174 CG-SVX17D-EN
Diagnostics
Fault Detected: Evaporator Water
Pump 2
Fault Detected: Evaporator Water
Pump 2
Fault: Evap Water Pump
Chiller Normal or
Warning and
Special Action
NonLatch All
For systems with no evaporator pump
or a single evaporator pump, a normal
shutdown shall be performed. For
multiple pump systems, detection of a
pump fault will generally cause pump
control to switch to the redundant
pump. See “Chilled Water Pump
Control - Field Supplied Dual Pumps,
p. 82 for more details.
Remote
Fan Fault
Fan Fault
Fan Fault
Circuit Warning Latch All The fan deck is indicating a fault. Local
Fan Inverter Fault
Fan Inverter Fault
Fan Inverter Fault
Circuit Warning NonLatch All
The fan inverter fault input is ignored
for the first 5 seconds of start up to
allow variable speed drives to power
up.
Local
Low Suction Superheat
Low Suction Superheat
Low Suction Superheat
Circuit Immediate Latch
Ckt Energized
[Ckt Not
Energized]
Measured suction superheat stays
below 2.22 °C for one continuous
minute, with a 1 minute ignore time fro
m the start of the circuit.
Suction Superheat = suction temp –
sat. suction temp.
Local
High Compressor Pressure Differential
High Compressor Pressure Differential
High Cprsr Press Diff
Circuit Immediate Latch
Ckt Energized
[Ckt Not
Energized]
Compressor involute pressure
differential (discharge pressure
[absolute] – volume ratio * suction
pressure [absolute]) exceeds 2550 kPa
differential, or exceeds 1862 kPa
differential for 30 continuous minutes.
Nominal volume ratio for R410A
compressors is 2.9.
Local
Low Differential Refrigerant Pressure
Low Differential Refrigerant Pressure
Low Differential Rfgt Press
Circuit Normal Latch
Ckt Energized
[Ckt Not
Energized]
The system differential pressure for
the respective circuit was below 90
psid for more than 4000 psid-sec, with
a 2.5 minute ignore time from the start
of the circuit.
Local
Low Discharge Saturated Temperature
Low Discharge Saturated Temperature
Low Discharge Sat Temp
Circuit Normal Latch
Ckt Energized
[Ckt Not
Energized]
The discharge saturated temperature
for the respective circuit was below 20
°C for more than 3750 °C-sec, with a
10 minute ignore time from the start of
the circuit. Integration starts after the
ignore time is completed.
Local
Software Error 1001: Call Trane Service
Software Error 1001: Call Trane Service
Software Error 1001
All
functions
Immediate Latch All
A software monitor has detected a
condition in which there was a
continuous 1 minute period of
compressor operation, with no
Evaporator water flow. The presence of
this software error message suggests
an internal software problem has been
detected. The events that led up to this
failure, if known, should be recorded
and transmitted to Trane Controls
Engineering.
Local
Software Error 1002: Call Trane Service
Software Error 1002: Call Trane Service
Software Error 1002
All
functions
Immediate Latch All
A software monitor has detected a
condition in which there was a
continuous 1 minute period of
compressor operation, with a
misaligned state machine.
Reported if state chart misalignment
occurred inferred form the Capacity
Control, Circuit, or Compressor State
Machines being in Stopped state or
Inactive state while a compressor was
operating and this condition existed for
at least 1 minute. The presence of this
software error message suggests an
internal software problem has been
detected. The events that led up to this
failure, if known, should be recorded
and transmitted to Trane Controls
Engineering.
Local