16 Wireless Zone Sensor • BAS-SVX04A-EN
Setting the Address, Mounting, Wiring, and Associating the
Receiver and Sensor
Setting the Receiver Address
1. Using a small screwdriver, set the three rotary address switches (locations
S1, S2, S3) on the receiver (Figure 3, p. 15) to an address between 001 and
999.
Note: • Do not use 000 as an address for installation. If you set the receiver
address to 000, it will:
– Returns the receiver outputs to their factory defaults indefinitely
(zone temperature and setpoint outputs: 72.5
°F [22.5°C])
– Remove all association knowledge
– Make the receiver unable to associate with a sensor
• Read the switches from left to right in the order in which they are
numbered (S1, S2, S3).
• Zero is at the 9 o’clock position.
2. Make a notation of the address and location of the receiver.
Setting the Sensor Address
1. Using a small screwdriver, set the three rotary address switches (locations
S1, S2, S3) on the sensor (Figure 3, p. 15) to the same address used for the
receiver it is to be associated with.
2. Make a notation of the address and location where this sensor is to be
mounted.
Note: • Do not use 000 as an address for installation. If you set the address
to 000, it will:
– Remove all association knowledge
– Revert to a low-power hibernation mode.
– Send a disassociation request to the receiver. If the sensor and
receiver are associated and communicating at the time the
sensor is set to 000 and the Test button is pressed, the receiver
will also become unassociated and will be available for re-
association.
• Read the switches from left to right in the order in which they are
numbered (S1, S2, S3).
• Zero is at the 9 o’clock position.
3. Make a notation of the address and location of the sensor.