EasyManuals Logo
Home>Uponor>Temperature Controller>SmatrixMove

Uponor SmatrixMove User Manual

Uponor SmatrixMove
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #67 background imageLoading...
Page #67 background image
The maintenance of Uponor Smatrix Move/Move PLUS
includes the following:
Manual preventive maintenance
Automatic preventive maintenance
Corrective maintenance
11.1 Manual preventive maintenance
Uponor Smatrix Move/Move PLUS requires no
preventive maintenance except cleaning:
1. Use a dry soft cloth to clean the components.
STOP!
Do not use any detergents to clean
the Uponor Smatrix Move/Move PLUS
components.
11.2 Automatic preventive maintenance
The controller is fitted with an automatic valve and
pump exercise function. The function is designed to
prevent the pump and actuators from seizing up due
to inactivity. The valve and pump exercise function is
enabled from the factory and can be disabled in the
system parameters.
See section 8 Operate the Uponor Smatrix Move/Move
PLUS controller for more information.
The function is activated at noon (12:00) if the valve
and pump has not been operated for a period of
24 hours.
12:00 The pump is activated for 1 minute.
12:01 The actuator opens, operation takes 2 minutes.
12:03 The actuator closes, operation takes 2 minutes.
11.3 Corrective maintenance
Fallback mode
If a thermostat is malfunctioning or not detected,
the controller executes a fallback mode in an attempt
to maintain the temperature in the zone (heating or
cooling) until the problem is resolved.
11 Maintenance
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
67
UPONOR SMATRIX MOVE/MOVE PLUS
·
INSTALLATION AND OPERATION MANUAL

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Uponor SmatrixMove and is the answer not in the manual?

Uponor SmatrixMove Specifications

General IconGeneral