ACH550 E-Clipse Bypass User’s Manual 2-247
Technical data
Motor connections (supplement to ACH550-UH Users Manual)
Motor Terminals
See Drive’s power connection terminals above.
Bypass Contactors
The bypass circuit available with the ACH550 E-Clipse Bypass includes two
contactors. One contactor is the bypass contactor (2M) that can be used to manually
connect the motor directly to the incoming power line in the event that the ACH550 is
out of service. The other contactor is the ACH550 output contactor (1M) that
disconnects the ACH550 from the motor when the motor is operating in the Bypass
mode. The drive output contactor and the bypass contactor are interlocked to
prevent “back feeding,” applying line voltage to the ACH550 output terminals.
Motor Overload Protection
Motor overload protection is set using the ACH550 drive control panel. (Refer to
ACH550-UH Users manual.) The overload protection parameters set on the
ACH550 drive are used by both the drive and the bypass.
In the Drive mode, motor overload protection is provided by the ACH550.
In the Bypass mode, motor overload protection is provided by the bypass control
board.
WARNING! If power is applied and the switches and contacts in the control circuit
are commanding the motor to run, the motor will start as soon as the overload
protection is reset.
Use caution when resetting the overload protection to make sure it is safe to start the
motor.

Table of Contents

Other manuals for ABB ACH550-VCR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACH550-VCR and is the answer not in the manual?

ABB ACH550-VCR Specifications

General IconGeneral
BrandABB
ModelACH550-VCR
CategoryController
LanguageEnglish

Related product manuals