1-60 ACH550-UH User’s Manual
Application macros
Floating Point macro
This application macro is for applications where speed reference needs to be
controlled through digital inputs (DI5 & DI6). By activating digital input 5, the speed
reference increases, by activating digital input 6, the speed reference decreases. If
both digital inputs are active or inactive, the reference does not change.
Note: When constant speed 1 is activated using digital input 3 (DI3), the reference
speed is the value of parameter 1202. The value remains as the reference speed
when digital input 3 is deactivated.
Parameters Changed Relative to HVAC Default
Parameter Value
Parameter Value
9902
APPLIC MACRO 10 (FLOATING PNT) 3416 SIGNAL 3 MIN -200.0%
1103
REF1 SEL 7 (DI5U, 6D) 3417 SIGNAL 3 MAX 200.0%
1401
RELAY OUTPUT 17 (STARTED) 3419 OUTPUT 3 UNIT 4 (%)
1601
RUN ENABLE 2 (DI2) 3420 OUTPUT 3 MIN -200.0%
3415
SIGNAL 3 PARAM 0105 (TORQUE) 3421 OUTPUT 3 MAX 200.0%
1SCR
2AI1
3AGND
410V
5AI2
6AGND
7AO1
8AO2
9AGND
10 24V
11 GND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
19 RO1C
20 RO1A
21 RO1B
22 RO2C
23 RO2A
24 RO2B
25 RO3C
26 RO3A
27 RO3B
X1
mA
mA
Not configured
Reference voltage 10 VDC
Output frequency: 0(4)…20 mA
Start/Stop: Activate to start drive
Run permissive: Deactivate to stop drive (P 1601)
Constant (Preset) speed 1 (P 1202)
Safety interlock 1: Deactivate to stop drive (P 1608)
Reference up: Activate to increase reference (P 1103)
Relay output 1 (P 1401)
Default operation: Started =>19 connected to 21
Relay output 2 (P 1402)
Default operation: Running =>22 connected to 24
Relay output 3 (P 1403)
Default operation: Fault (-1) =>25 connected to 27
Output current: 0(4)…20 mA
Reference down: Activate to decrease reference (P 1103)
Analog input circuit common
Not configured
Analog output circuit common
Auxiliary voltage output +24 VDC
Auxiliary voltage output common
Digital input common for all
Signal cable shield (screen)
Analog input circuit common
(Fault => 25 connected to 26)
J1
AI1: 0(4)
20 mA
AI2: 0(4)
20 mA
ON
J1 Jumper Settings
ON
ON
12
J1

Table of Contents

Other manuals for ABB ACH550-VCR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACH550-VCR and is the answer not in the manual?

ABB ACH550-VCR Specifications

General IconGeneral
BrandABB
ModelACH550-VCR
CategoryController
LanguageEnglish

Related product manuals