Control unit 85
Connection examples of two-wire and three-wire sensors to analog input 2
(ANALOG IN/OUT)
Hand/Auto, Hand/PID, and PID macros use analog input AI2.
Note: The maximum capability of the auxiliary voltage output (24 V DC [250 mA]) must not
be exceeded.
An example of a two-wire sensor/transmitter supplied by the drive auxiliary voltage output
is shown below. Set the input signal to 4…20 mA, not 0…20 mA
An example of a three-wire sensor/transmitter supplied by the drive auxiliary voltage
output is shown below.
DI6 as frequency input
If DI6 is used as a frequency input, see the firmware manual for how to set parameters
accordingly.
5 AI2 Process actual value measurement or reference,
0(4)…20 mA, R
in
= 100 ohm
6AGND
…
10 +24V Auxiliary voltage output, non-isolated,
+24 V DC, max. 250 mA
11 DGND
4…20 mA
+
-
P
I
5 AI2 Process actual value measurement or reference,
0(4)…20 mA, R
in
= 100 ohm
6AGND
…
10 +24V Auxiliary voltage output, non-isolated,
+24VDC, max. 250mA
11 DGND
(0)4…20 mA
+
-
OUT
P
I