NR-DOL STARTER
NR_DOL starter is a basic starter type for
driving motor in one direction. When start
command has been received from fieldbus
or local I/O, the contactor control output will
be energized and remains in this in condition
until stop command has been received or
any protection function is activated.
Name Pin Description
CCLI X4:6 Contactor control voltage input
CCA X4:7 Contactor control A
DI6(F_Ca) X1:7 Contactor control A feedback
DI5(Loc/R) X1:6 Local/remote control switch input

14 Timing diagram of control sequence NR-DOL
* The assigned DI and PIN code may change in actual design
Operating sequence
• Starting Sequence: Motor is stopped
and ready to startSTART command
(Start 1) received Internal CCA contact closed
and remain closedFeedback received
• Stopping Sequence: Motor is running
STOP command receivedInternal CCA
contact openFeedback received
Contactor feedback and current feedback
are both used for verification of the mo-
tor status. Any unexpected feedback re-
sults in alarm or fault.
Contactor feedback can be disabled
through parameter. Current feedback r is
always on the background to ensure the
completion of an expected operation
sequence. The feedback time is adjustable.
0 4 . MOTOR STARTERS CONTROL
23

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB M10 Series and is the answer not in the manual?

ABB M10 Series Specifications

General IconGeneral
BrandABB
ModelM10 Series
CategoryController
LanguageEnglish

Related product manuals